无码另类,亚洲五月婷,av黑人床战,中文久久久久久

DJC-KR Combustible Gas Detection Alarm Device


Combustible gas alarm system uses the combustible gas density detector installed on site to detect the density of combustible gas in the pump compartment and living areas. The detector will changeover the density of the combustible gas into 4-20 mA signals and send to the Data Collector Module which, in turn, changes the signals into digital signals and send to the LCD (liquid crystal display) unit by the CAN bus. The Liquid Crystal Display unit can be installed in the bridge, centralized control room and many other places to simultaneously display the combustible gas density. Once the density of the combustible gas has reaches the pre-alarm value and the alarm value (which can be modified), the system will generate audible and visible alarm signal.

Combustible gas sensor
KR800 Combustible gas detector was designed by DONJUN;
Suitable for hydrocarbon concentration monitoring and alarm; 
LCD display;
4-20mA signal or RS485 communication;
Suitable for detecting and warning of potential explosive,toxic,hypoxia etc. 



Technical parameter:
Ex: Exia II CT4
Measure range: 0 ~ 100 %LEL
Measure precision: ± 5 %LEL
Temperature: - 10 ℃~ 60 ℃
Power supply: 12 ~24 VDC
Output: 4–20 mA



Explosion Protection Audio and Visual Alarm
Technical Parameters:
Voltage: AC220V/DC24V
Color: red
Light: LED
Sound grade: 75dB
Material: Aluminum
Ex: Exia IICT6
IP: IP65